We’d like to use analytics cookies to see how people use the site, and marketing tools that show which companies visit. They only run if you say yes.
Read the cookie policy
Installed with a Floodline® Ranger Control Panel, the cable senses the liquid, triggers an alarm and pinpoints the location of the leak to within one metre. Andel Ranger Hydrocarbon Fuel Detection Cable provides distributed leak detection and location for a wide range of applications, and is available in a variety of lengths to provide as much coverage as needed.
Benefits at a glance
Pinpoints the leak location within one metre
Available in a variety of lengths
Rugged construction
Reliable in demanding environments
Quick and easy installation
Mechanically strong and chemically resistant
Distributed monitoring
These modular sensing cables may be connected in series to provide distributed monitoring for trenches, subfloors and double-containment piping, or used individually for double-containment tanks, sumps and small areas.
Rugged construction
Radiation-crosslinking and conductive-polymer technology is used to make the cable mechanically strong and chemically resistant. The core is constructed of two sensing wires, an alarm signal wire and a continuity wire. The core is encased in a conductive-polymer jacket and surrounded with a fluoropolymer braid, allowing the cable to perform reliably in the most demanding environments.
Note
Response times are affected by operating temperature. Consult Andel for specific response times at other temperatures and in other liquids.
An undetected leak can shut down a data centre.
Or close a hospital ward, or trigger a legal claim. Catching it early is always cheaper than the alternative.
Andel Floodline doesn’t just prevent damage. It demonstrates due diligence. Insurers increasingly expect leak detection in high-risk environments, and early warning systems materially reduce premiums, claims exposure and litigation risk.
The Shard
Houses of Parliament
Canary Wharf
London 2012 Olympics
No handoff, no gaps, one number to call.
The detail.
Product code: RHFDC.
Standards: ASTM D 543.
Product characteristics
Cable diameter8mm nominal (13mm nominal with connector)
Cable weight7.3 kg/100m nominal
Fluoropolymer braid colourRed, white and black
Operating temperature range-20°C to 60°C
Pull force limitNot to exceed 22.7 kg (50 lb)
Bend radius50mm (minimum)
PressureLoads greater than 9 kg per linear inch at 20°C may immediately trigger an alarm
Non-resettableMust be replaced after exposure
Chemical resistance
Tested toCable functions normally after exposure in accordance with ASTM D 543 at 23°C for seven days